Document LTP0101 rev 2a

 

Page Location: Home > Installation > Service Level Programming > Service Level Factory Defaults

Service Level Programming

CAUTION - Failure to heed the following may result in equipment damage.

  • Service Level Programming must only be attempted by authorized personnel.
  • Unauthorized adjustments in the Service Menu (beyond the LOC menu) may void the heat pump's warranty.
  • Resetting the microprocessor to access a locked keypad will reset all settings to factory default including any installer-entered configuration. Re-programming all custom site condition settings will be required when using this reset. See "Reset to Factory Defaults Settings"

Please note -

Before changing multiple program options, it is recommended that the user lock option be disabled. See "User Lock Option (Disable)"

The lockout option can be re-enabled after all changes are completed.

Service Level Factory Defaults

Certain programming options have been preset at the factory. These options can be overwritten for certain site-specific conditions.

Table 3 - Default Program Parameters Chart
CODE DESCRIPTION DEFAULT VALUE RANGE

CFO

Call-Flex Options 0 Set to off at the factory.

dBP

Pool Dead-Band Differential Set at factory. Do not adjust.

dB5

Spa Dead-Band Differential Set at factory. Do not adjust.

DEL

Compressor Time Delay 1 (4 minutes) Set to on (at 4 minutes) at the factory. Do not adjust.

dSC

Defrost Sensor Factory Calibrated Set at factory. Do not adjust.

dFd

Defrost Delay Factory Calibrated Set at factory. Do not adjust.

FS2

Flow Switch / Automatic Thermostat Switching Option 0
0 = "No Switch"
1 = "Enable Switch"

JAO

External Controller 0
0 = "No Controller"
2 = "Two Wire Controller"
3 = "Three Wire Controller"

LOC

Service Level Entry Point 50 00 - 99

tSC

Water Sensor Factory Calibrated Set at factory. Do not adjust.